Copper pipes

1.Copper pipes

1.1Conditioning copper pipes manufactured to ASTM B290 confirmed, PED 97/23, AD2000

Diameter inch Diameter mm Thickness mm Weight, kg / m Maximum pressure, bar
1/4 6.35 0.80 0.12 133
3/8 9.52 0.81 0.199 84
1/2 12.70 0.81 0.271 62
5/8 15.87 0.89 0.373 62
3/4 19.05 1.00 0.454 51

1.2 Refrigeration copper pipes manufactured in accordance with EN 12735, EN 13348

outer diameter Thickness mm Length, m Weight, kg / m
10 1,0 5 0.252
12 1,0 5 0.308
15 1,0 5 0.391
18 1,0 5 0.475
22 1,0 5 0.587
28 1,5 5 0.755
35 1,5 5 1.405
42 1,5 5 1.700
54 2,0 5 2.908
64 2,0 5 3.467
76 2,0 5 4.144
89 2,0 5 4.857

1.3 Copper plumbing pipes manufactured according to EN 1057

Outside diameter mm Thickness mm Length, m Maximum pressure, bar
15 1,0 3 86
18 1,0 3 71
22 1,0 3 57
28 1,0 3 54
35 1,0 3 43
42 1,0 3 35

1.4 Solar copper pipes

Outside diameter mm Thickness mm Maximum pressure, bar
12 0.60 48
15 0.70 45
18 0.75 40
22 0.90 39

1.5 Pre-insulated copper pipes

Outside diameter inch Pipe outside diameter, mm Insulation thickness, mm Maximum pressure, bar
1/4 6.35 6,0 133
3/8 9.52 6,0 84
1/2 12.70 6,0 62
5/8 15.87 6,0 62

2.Insulation

armacell-361cg-11

 

2.1Circular insulation insulation
Specifications:

-Temperature range: -50 ° C to + 105 ° C

-Thermal conductivity λ: ≤0.035 W / (m ∙ K) at 0 ° C

≤0.039 W/(m∙K) la 40°C

Ø, mm The thickness of 6 mm The thickness of 9 mm Thickness 13 mm Thickness 19 mm Thickness 25 mm
6 6×06
10 6×10
12 6×12 9×12 13×12
15 6×15 9×15 13×15
18 6×18 9×18 13×18
22 6×22 9×22 13×22 19×22 25×22
28 9×28 13×28 19×28 25×28
35 9×35 13×35 19×35 25×35
42 9×42 13×42 19×42 25×42
54 9×54 13×54 19×54 25×54
64 9×64 13×64 19×64 25×64
76 13×76 19×76 25×76
89 13×89 19×89 25×89
108 13×108 19×108

2.2   Plates

Nominal thickness: 9 mm, 13 mm, 19 mm